Base Mounted Axial Flow Fan — Manufacturer & Supplier, India
Vayuvents manufactures Base Mounted Axial Flow Fans for permanent floor installation in factories, process plants, and large industrial buildings. 305 mm to 1,830 mm dia, IS 3588 compliant. Manufacturer & supplier in Mumbai. Call +91 90961 88703.
A Base Mounted Axial Flow Fan is a direct-drive axial fan installed on a rigid fabricated steel base plate that is permanently bolted to the factory floor or structural plinth. Unlike stand-mounted fans that can be repositioned, base-mounted fans provide a fixed, vibration-stable installation point ideal for large fan diameters and high-power motors where stability is critical.
Vayuvents manufactures base mounted axial fans at our Vasai, Mumbai works in diameters from 305 mm to 1,830 mm with motor powers from 0.25 HP to 50 HP. The base plate is engineered to the fan weight and motor torque reaction — distributing loads evenly and eliminating the vibration and movement that affects stand-mounted configurations at large fan sizes.
Base mounted axial fans are the preferred configuration for high-capacity fresh air supply and exhaust in large-span industrial buildings, for permanent installation at process equipment cooling inlets, and for cooling tower, air-cooled heat exchanger, and condenser fan service where the fan cannot be relocated after installation.
Export supply available to UAE, Saudi Arabia, Qatar, Oman, and other countries with full IS 3588 documentation, certificate of origin, and material certificates.
Key Features & Benefits
Rigid Base Plate
Heavy-gauge MS welded base plate bolted to floor — eliminates movement and vibration at large fan diameters and high motor powers for stable continuous operation.
Direct Drive
Motor directly coupled to impeller shaft — no belts, no pulleys, maximum power transmission efficiency, zero belt maintenance cost.
Fixed Permanent Installation
Designed for permanent bolted-down installation — ideal where the fan position is determined by the building or process layout and cannot change.
IS 3588 Impeller
Aerodynamic aluminium alloy or MS impeller, dynamically balanced, tested per IS 3588-1987 — ensures smooth, vibration-free operation throughout the service life.
IP55 Motor
IP55 TEFC motor as standard — suitable for dusty factory floors, humid process buildings, and outdoor covered installations.
High Airflow Range
305 mm to 1,830 mm diameter covers 1,800 m³/hr to 1,50,000 m³/hr — matches any factory or process plant fresh air and exhaust ventilation requirement.
Anti-Vibration Mounts
Anti-vibration isolator pads between base plate and floor — reduces structure-borne vibration transmission to building fabric and neighbouring equipment.
IS 3588 Compliant
Performance tested per IS 3588-1987 with airflow and motor power test certificate supplied with every fan.
Technical Specifications
| Parameter | Specification |
|---|---|
| Fan Diameter Range | 305 mm (12") to 1,830 mm (72") |
| Airflow (Free Air) | 1,800 m³/hr to 1,50,000 m³/hr |
| Motor Power Range | 0.25 HP to 50 HP |
| Motor Speed | 960 / 1,440 / 2,800 RPM |
| Motor Enclosure | IP55 TEFC (standard) |
| Motor Insulation | Class F |
| Power Supply | 415V 3-Phase 50Hz | 230V Single-Phase available |
| Impeller Material | Aluminium alloy die-cast / MS |
| Casing Material | MS fabricated, epoxy primer + finish coat |
| Standards | IS 3588-1987 | IS 4894 |
Airflow Performance — Model Range
| Sr. | Model | Dia (mm) | Motor (HP/Pole) | RPM | Free Air (m³/hr) | @10 mmWG | @15 mmWG | @20 mmWG | @25 mmWG | @30 mmWG |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | AX-75-28-120 | 305 | 0.75/2P | 2800 | 2,300 | 2,000 | 1,750 | 1,400 | — | — |
| 2 | AX-25-14-120 | 305 | 0.25/4P | 1440 | 1,800 | 1,500 | 1,450 | 1,320 | — | — |
| 3 | AX-50-14-150 | 385 | 0.50/4P | 1440 | 2,250 | 1,200 | — | — | — | — |
| 4 | AX-75-28-150 | 385 | 0.75/2P | 2850 | 5,000 | 4,100 | 3,900 | 3,700 | 3,300 | 3,000 |
| 5 | AX-50-14-180 | 460 | 0.50/4P | 1440 | 6,750 | 5,500 | 4,400 | — | — | — |
| 6 | AX-100-28-180 | 460 | 1.0/2P | 2880 | 9,000 | 7,500 | 6,200 | — | — | — |
| 7 | AX-100-14-240 | 612 | 1.0/4P | 1440 | 12,000 | 11,000 | 10,900 | 9,500 | — | — |
| 8 | AX-200-28-240 | 612 | 2.0/2P | 2800 | 15,500 | 13,600 | 13,000 | 11,300 | — | — |
| 9 | AX-150-14-280 | 712 | 1.5/4P | 1440 | 17,500 | 15,000 | 13,900 | 12,500 | 11,800 | 10,000 |
| 10 | AX-300-28-280 | 712 | 3.0/2P | 2880 | 20,000 | 18,500 | 16,900 | 16,000 | 15,000 | 14,500 |
| 11 | AX-300-96-360 | 915 | 3.0/6P | 960 | 45,000 | 42,000 | 39,000 | 37,000 | 34,000 | — |
| 12 | AX-500-14-360 | 915 | 5.0/4P | 1440 | 40,000 | — | — | 38,000 | 35,000 | 32,000 |
| 13 | AX-500-96-400 | 1015 | 5.0/6P | 960 | 48,000 | 45,000 | 43,000 | 42,000 | — | — |
| 14 | AX-750-14-400 | 1015 | 7.5/4P | 1440 | 55,000 | 49,000 | 47,000 | — | — | — |
| 15 | AX-750-96-480 | 1220 | 7.5/6P | 960 | 65,000 | — | 58,000 | 55,000 | 34,500 | 30,500 |
| 16 | AX-100-960-480 | 1220 | 10/6P | 960 | 69,000 | — | — | 65,000 | 61,500 | 60,000 |
| 17 | AX-150-960-600 | 1530 | 15/6P | 960 | 75,000 | — | — | — | — | 80,000 |
| 18 | AX-300-14-600 | 1530 | 30/4P | 1440 | 95,000 | — | — | — | — | — |
| 19 | AX-300-96-720 | 1830 | 30/6P | 960 | 1,20,000 | — | — | — | — | — |
| 20 | AX-500-14-720 | 1830 | 50/4P | 1440 | 1,50,000 | — | — | — | — | — |
- Fan selection based on air at 20°C, density 1.2 kg/m³.
- Performance and tolerance as per IS 3588-1987.
- Custom sizes and intermediate performance points available on request.
Product Images




Where It Is Used
- Large-span factory buildings requiring permanent fresh air supply fans
- Process plant buildings — permanent exhaust ventilation for heat and fumes
- Cooling tower fan replacement and new cooling tower installations
- Air-cooled heat exchanger and condenser fan service
- Power station cooling fan service — auxiliary cooling systems
- Steel plant and foundry building general ventilation
- Textile mill humidification supply fan permanent installation
- Pharmaceutical plant clean room supply air makeup units
- Cement plant building ventilation and raw mill area cooling
- Shipyard fabrication shed permanent fresh air supply
- Generator room permanent ventilation and heat exhaust
- Underground car park permanent jet fan or supply fan installation
You May Also Need

Stand Mounted Fresh Air Fan
Height-adjustable stand mount — flexible positioning without permanent fixing.
View Details →
Flameproof Floor Mounted Fan
IS 5572 Ex-d certified floor mount for Zone 1 & Zone 2 hazardous areas.
View Details →
Wall Mounted Tube Axial Fan
Through-wall installation for compact exhaust and fresh air supply.
View Details →
Belt Driven Axial Fan
Belt drive option for high-temperature and corrosive airstream service.
View Details →FAQs — Base Mounted Axial Flow Fan
A base mounted axial fan is bolted permanently to the floor on a rigid fabricated steel base plate — it cannot be repositioned after installation. A stand mounted fan sits on an adjustable pedestal that can be moved to different locations. Base mounting is chosen for large fans (above 600 mm diameter), high motor powers (above 5 HP), and permanent process plant and building ventilation installations where stability and vibration control are more important than flexibility.
For a 5,000 sq m factory with 8 metre ceiling height and 6 air changes per hour, the required airflow is approximately 2,40,000 m³/hr. This is typically provided by 2 to 3 fans of 1,220 mm to 1,530 mm diameter (AX-750-96-480 to AX-150-960-600 range). Vayuvents provides free sizing calculations based on your factory dimensions, ceiling height, and required air change rate.
Yes. Base mounted axial fans with IP55 motors and epoxy-painted casings are suitable for outdoor installation in covered or semi-covered areas. For fully exposed outdoor installations, IP65 motors and additional anti-corrosion paint treatment are recommended. Vayuvents supplies fans for outdoor service with appropriate motor enclosure and paint specification on request.
Vayuvents supplies base mounted fans with a fabricated MS base plate with pre-drilled anchor bolt holes. The base plate is fixed to the concrete floor plinth using M16 or M20 anchor bolts (4 to 6 bolts depending on fan size). Anti-vibration pad sets are supplied for placement between the base plate and floor surface. Vayuvents provides the anchor bolt layout drawing and recommended plinth dimensions with each fan.
Base mounted axial fans can be installed with the airflow axis horizontal (blowing across the factory floor), vertical upward (exhausting through a roof opening or duct), or at an angle. The most common industrial installation is horizontal airflow for cross-ventilation or directed cooling. A flanged casing outlet can be fitted to connect to ductwork for directed supply or exhaust if required.
Standard sizes (305 mm to 1,220 mm, up to 10 HP) are typically available within 2 to 3 weeks. Larger sizes (1,530 mm to 1,830 mm, 15 HP to 50 HP) require 4 to 6 weeks. Custom configurations, special materials, and export orders with third-party inspection may require 6 to 8 weeks. Vayuvents confirms delivery schedule at the time of order placement.
Contact Vayuvents at enquiry@vayuvents.com or call +91 90961 88703. Share the required airflow in m³/hr or fan diameter, installation type (horizontal / vertical), motor power, and any special requirements (flameproof, corrosion-resistant, outdoor). We will provide a technical selection and commercial proposal within 24 hours.